R - Values for Single Wythe
Concrete Masonry Walls
TEK 6-2A (Energy & IAQ 1996)
INTRODUCTION
Concrete Masonry walls are often constructed of hollow units with cores filled with loose fill material and/or grout. This construction method provides the minimum wall thickness, while allowing insulation and reinforcement to be included to increase thermal and structural performance, respectively.
Determining the thermal insulation values of these walls, however, can be time consuming, especially when the wall is composed of several materials. This TEK facilitates the determination of thermal resistance (R) and thermal transmittance (U) of these single wythe concrete masonry walls.
R-VALUE TABLES
Tables of calculated R-values for hollow block of 6, 8, 10 and 12 in. (152, 203, 254, and 305 mm) thickness, for concrete densities of 85 to 135 lb/ft3 (1362 to 2163 kg/m3) are included. In addition, Table 1 shows the approximate percentage of grouted and ungrouted wall area for different vertical and horizontal grout spacings, which can be used to determine R-values of partially grouted walls. Thermal properties used in compiling the tables are listed in Table 6.
In addition to the core insulations listed in Tables 2 through 5, polystyrene inserts are available which fit in the cores of concrete masonry units. Inserts are available in many shapes and sizes to provide a range of insulating values and accommodate various construction conditions. Specially designed concrete masonry units may incorporate reduced-height webs to accommodate inserts. Such webs also reduce thermal bridging through masonry, since the reduced web area provides a smaller cross-sectional area for heat flow through the wall. To further reduce thermal
bridging, some manufacturers have developed units with two cross webs rather than three. In addition, some inserts have building code approval to be left in the grouted cores, thus improving the thermal performance of fully or partially grouted masonry walls.
The ASHRAE series-parallel method (also called isothermal planes) (ref.1) was used to calculate the base case values (i.e., the row Exposed block, both sides) in Tables 2 through 5. This method accounts for the thermal bridging through the webs of concrete masonry units. R-values of the various finish systems are added to these base values. To determine R-values for walls with 2 in. (51 mm) of rigid insulation (expanded polystyrene, extruded polystyrene, or polyisocyanurate) rather than the 1 in. (25mm) shown in the tables, simply add the appropriate insulation thermal resistivity value from Table 6 to the R-values in Tables 2 through 5.
R-values of concrete masonry walls are correlated to concrete density, since thermal conductivity of concrete increases with increasing density. Tables 2 through 5 list a range of R-values for each density, as well as a single value, which represents a calculated middle-of-the-range. The U-factor is determined by simply inverting the R-value (i.e., U = 1/R).
A range of thermal values is appropriate for concrete products because the thermal conductivity of concrete cannot always be accurately estimated from density alone. The thermal conductivity of concrete varies with aggregate types(s) used in the concrete mix, the mix design, moisture content, etc.
These published values reflect a compendium of historical data on thermal conductivity of concrete (refs. 1,3). Locally available products and local conditions may result in thermal values which fall outside of this range. The middle-of-the-range values are presented for use in cases where more accurate values are not available from local manufacturers.
The values for insulated and grouted cores in Tables 1 through 5 are based on the assumption that all masonry cores are either insulated or grouted. That is, for walls which are either not grouted or are fully grouted, the values in Tables 2 though 5 can be used directly.
| Table 1 - Percent Ungrouted Area/Percent Grouted Area For Partially Grouted Walls |
| Vertical grout spacing, in. (mm) |
| no vert. grout | 48
(1219) |
40
(1016) |
32
(813) |
24
(610) |
16
(406) | |
| no horiz. grout | 100
0 |
83
17 |
80
20 |
75
25 |
67
33 |
50
50 |
| 48 (1219) | 83
17 |
69
31 |
67
33 |
63
37 |
56
44 |
42
58 |
| 40 (1016) | 80
20 |
67
33 |
64
36 |
60
40 |
53
47 |
40
60 |
| 32 (813) | 75
25 |
63
37 |
60
40 |
56
44 |
50
50 |
37
63 |
| 24 (610) | 67
33 |
56
44 |
53
47 |
50
50 |
44
56 |
33
67 |
| 16 (406) | 50
50 |
42
58 |
40
60 |
37
63 |
33
67 |
25
75 |
| Table 2 - R-Values for 6 in. (152 mm) Concrete Masonry Walls, hr.ft2.oF/Btua |
| Cores filled withb: |
| Construction | Density of concrete, | Cores
empty |
Loose-fill insulation Perlite Vermiculite |
Polyurethane
foamed insulation |
Solid grouted |
| pcf | range | mid | range | mid | range | mid | range | mid | range | mid | |
| Exposed block,
both sides |
85
95 105 115 125 135 |
2.2-2.5
2.1-2.4 2.0-2.2 1.8-2.1 1.7-2.0 1.6-1.9 |
2.4
2.2 2.1 2.0 1.8 1.7 |
4.8-6.1
4.1-5.4 3.5-4.8 3.0-4.2 2.5-3.7 2.2-3.2 |
5.3
4.6 4.0 3.4 3.0 2.6 |
4.5-5.6
3.9-5.0 3.3-4.5 2.9-4.0 2.5-3.5 2.2-3.1 |
5.0
4.3 3.8 3.3 2.9 2.5 |
5.2-7.0
4.4-6.1 3.7-5.2 3.1-4.5 2.6-3.9 2.2-3.4 |
5.9
5.0 4.3 3.6 3.1 2.7 |
1.6-1.8
1.5-1.7 1.4-1.6 1.4-1.5 1.3-1.5 1.3-1.4 |
1.7
1.6 1.5 1.4 1.4 1.3 |
| ½ in. (13 mm) gypsum board on furring | 85
95 105 115 125 135 |
3.6-3.9
3.5-3.8 3.4-3.6 3.2-3.5 3.1-3.4 3.0-3.3 |
3.8
3.6 3.5 3.4 3.2 3.1 |
6.2-7.5
5.5-6.8 4.9-6.2 4.4-5.6 3.9-5.1 3.6-4.6 |
6.7
6.0 5.4 4.8 4.4 4.0 |
5.9-7.0
5.3-6.4 4.7-5.9 4.3-5.4 3.9-4.9 3.6-4.5 |
6.3
5.7 5.2 4.7 4.3 3.9 |
6.6-8.4
5.8-7.5 5.1-6.6 4.5-5.9 4.0-5.3 3.6-4.8 |
7.3
6.4 5.7 5.0 4.5 4.1 |
3.0-3.2
2.9-3.1 2.8-3.0 2.8-2.9 2.7-2.9 2.7-2.8 |
3.1
3.0 2.9 2.8 2.8 2.7 |
| 1 in. (25 mm) expanded polystyrenec | 85
95 105 115 125 135 |
7.6-7.9
7.5-7.8 7.4-7.6 7.2-7.5 7.1-7.4 7.0-7.3 |
7.8
7.6 7.5 7.4 7.2 7.1 |
10.2-11.5
9.5-10.8 8.9-10.2 8.4-9.6 7.9-9.1 7.6-8.6 |
10.7
10.0 9.4 8.8 8.4 8.0 |
9.9-11.0
9.3-10.4 8.7-9.9 8.3-9.4 7.9-8.9 7.6-8.5 |
10.3
9.7 9.2 8.7 8.3 7.9 |
10.6-12.4
9.8-11.5 9.1-10.6 8.5-9.9 8.0-9.3 7.6-8.8 |
11.3
10.4 9.7 9.0 8.5 8.1 |
7.0-7.2
6.9-7.1 6.8-7.0 6.8-6.9 6.7-6.9 6.7-6.8 |
7.1
7.0 6.9 6.8 6.8 6.7 |
| 1 in. (25 mm) extruded polystyrenec | 85
95 105 115 125 135 |
8.6-8.9
8.5-8.8 8.4-8.6 8.2-8.5 8.1-8.4 8.0-8.3 |
8.8
8.6 8.5 8.4 8.2 8.1 |
11.2-12.5
10.5-11.8 9.9-11.2 9.4-10.6 8.9-10.1 8.6-9.6 |
11.7
11.0 10.4 9.8 9.4 9.0 |
10.9-12.0
10.3-11.4 9.7-10.9 9.3-10.4 8.9-9.9 8.6-9.5 |
11.3
10.7 10.2 9.7 9.3 8.9 |
11.6-13.4
10.8-12.5 10.1-11.6 9.5-10.9 9.0-10.3 8.6-9.8 |
12.3
11.4 10.7 10.0 9.5 9.1 |
8.0-8.2
7.9-8.1 7.8-8.0 7.8-7.9 7.7-7.9 7.7-7.8 |
8.1
8.0 7.9 7.8 7.8 7.7 |
| 1 in. (25 mm) polyiso-cyanurated | 85
95 105 115 125 135 |
12.1-12.4
12.0-12.2 11.8-12.1 11.7-12.0 11.6-11.9 11.5-11.8 |
12.2
12.1 12.0 11.8 11.7 11.6 |
14.6-16.0
13.9-15.3 13.3-14.6 12.8-14.1 12.4-13.5 12.1-13.1 |
15.2
14.5 13.8 13.3 12.8 12.4 |
14.3-15.5
13.7-14.9 13.2-14.3 12.7-13.8 12.3-13.4 12.0-13.0 |
14.8
14.2 13.7 13.2 12.7 12.4 |
15.1-16.9
14.2-15.9 13.5-15.1 12.9-14.4 12.5-13.8 12.0-13.2 |
15.8
14.9 14.1 13.5 13.0 12.5 |
11.5-11.7
11.4-11.6 11.3-11.5 11.2-11.4 11.2-11.3 11.1-11.3 |
11.6
11.5 11.4 11.3 11.2 11.2 |
| 2 x 4 furring with R13 batt & ½ in. (13 mm) gypsum board on furring | 85
95 105 115 125 135 |
13.0-13.3
12.9-13.2 12.8-13.0 12.6-12.9 12.5-12.8 12.4-12.7 |
13.2
13.0 12.9 12.8 12.6 12.5 |
15.6-16.9
14.9-16.2 14.3-15.6 13.8-15.0 13.3-14.5 13.0-14.0 |
16.1
15.4 14.8 14.2 13.8 13.4 |
15.3-16.4
14.7-15.8 14.1-15.3 13.7-14.8 13.3-14.3 13.0-13.9 |
15.7
15.1 14.6 14.1 13.7 13.3 |
16.0-17.8
15.2-16.9 14.5-16.0 13.9-15.3 13.4-14.7 13.0-14.2 |
16.7
15.815.1 14.4 13.9 13.5 |
12.4-12.6
12.3-12.5 12.2-12.4 12.2-12.3 12.1-12.3 12.1-12.2 |
12.5
12.4 12.3 12.2 12.2 12.1 |
a Notes: (hr.ft2.oF/Btu) (0.176) = m2.K/W. Mortar joints are in. (10 mm) thick, with face shell mortar bedding assumed. Unit dimensions based on Standard Specification for Loadbearing Concrete Masonry Units, ASTM C 90 (ref. 2). Surface air films are included.
b Values apply when all masonry cores are filled completely. Grout density is 140 pcf (2243 kg/m3). Lightweight grouts, which will provide higher R-values, are also available in some areas.c Installed over wood furring. Includes ½ in. (13 mm) gypsum board and nonreflective air space.
d Installed over wood furring, Includes ½ in. (13 mm) gypsum board and reflective air space.
| Table 3 - R-Values for 8 in. (203 mm) Concrete Masonry Walls, hr.ft2.oF/Btua |
| Cores filled withb: |
| Construction | Density of concrete, | Cores
empty |
Loose-fill insulation Perlite Vermiculite |
Polyurethane
foamed insulation |
Solid grouted |
| pcf | range | mid | range | mid | range | mid | range | mid | range | mid | |
| Exposed block,
both sides |
85
95 105 115 125 135 |
2.4-2.7
2.3-2.6 2.1-2.4 2.0-2.3 1.9-2.2 1.7-2.1 |
2.5
2.4 2.2 2.1 2.0 1.9 |
6.3-8.2
5.3-7.2 4.5-6.3 3.8-5.5 3.2-4.8 2.7-4.2 |
7.1
6.1 5.2 4.4 3.8 3.3 |
5.9-7.5
5.0-6.7 4.3-5.9 3.7-5.2 3.1-4.6 2.7-4.0 |
6.6
5.7 4.9 4.3 3.7 3.2 |
6.9-9.4
5.8-8.1 4.8-7.0 4.0-6.0 3.3-5.1 2.8-4.4 |
8.0
6.7 5.6 4.7 4.0 3.4 |
1.9-2.1
1.7-2.0 1.6-1.9 1.5-1.8 1.5-1.7 1.4-1.6 |
2.0
1.8 1.7 1.6 1.5 1.5 |
| ½ in. (13 mm) gypsum board on furring | 85
95 105 115 125 135 |
3.8-4.1
3.7-4.0 3.5-3.8 3.4-3.7 3.3-3.6 3.1-3.5 |
3.9
3.8 3.6 3.5 3.4 3.3 |
7.7-9.6
6.7-8.6 5.9-7.7 5.2-6.9 4.6-6.2 4.1-5.6 |
8.5
7.5 6.6 5.8 5.2 4.7 |
7.3-8.9
6.4-8.1 5.7-7.3 5.1-6.6 4.5-6.0 4.1-5.4 |
8.0
7.1 6.3 5.7 5.1 4.6 |
8.3-10.8
7.2-9.5 6.2-8.4 5.4-7.4 4.7-6.5 4.2-5.8 |
9.4
8.1 7.0 6.1 5.4 4.8 |
3.3-3.5
3.1-3.4 3.0-3.3 2.9-3.2 2.9-3.1 2.8-3.0 |
3.4
3.2 3.1 3.0 2.9 2.9 |
| 1 in. (25 mm) expanded polystyrenec | 85
95 105 115 125 135 |
7.8-8.1
7.7-8.0 7.5-7.8 7.4-7.7 7.3-7.6 7.1-7.5 |
7.9
7.8 7.6 7.5 7.4 7.3 |
11.7-13.6
10.7-12.6 9.9-11.7 9.2-10.9 8.6-10.2 8.1-9.6 |
12.5
11.5 10.6 9.8 9.2 8.7 |
11.3-12.9
10.4-12.1 9.7-11.3 9.1-10.6 8.5-10.0 8.1-9.4 |
12.0
11.1 10.3 9.7 9.1 8.6 |
12.3-14.8
11.2-13.5 10.2-12.4 9.4-11.4 8.7-10.5 8.2-9.8 |
13.4
12.1 11.0 10.1 9.4 8.8 |
7.3-7.5
7.1-7.4 7.0-7.3 6.9-7.2 6.9-7.1 6.8-7.0 |
7.4
7.2 7.1 7.0 6.9 6.9 |
| 1 in. (25 mm) extruded polystyrenec | 85
95 105 115 125 135 |
8.8-9.1
8.7-9.0 8.5-8.8 8.4-8.7 8.3-8.6 8.1-8.5 |
8.9
8.8 8.6 8.5 8.4 8.3 |
12.7-14.6
11.7-13.6 10.9-12.7 10.2-11.9 9.6-11.2 9.1-10.6 |
13.5
12.5 11.6 10.8 10.2 9.7 |
12.3-13.9
11.4-13.1 10.7-12.3 10.1-11.6 9.5-11.0 9.1-10.4 |
13.0
12.1 11.3 10.7 10.1 9.6 |
13.4-15.8
12.2-14.5 11.2-13.4 10.4-12.4 9.7-11.5 9.2-10.8 |
14.4
13.1 12.0 11.1 10.4 9.8 |
8.3-8.5
8.1-8.4 8.0-8.3 7.9-8.2 7.9-8.1 7.8-8.0 |
8.4
8.2 8.1 8.0 7.9 7.9 |
| 1 in. (25 mm) polyiso-cyanurated | 85
95 105 115 125 135 |
12.3-12.6
12.1-12.4 12.0-12.3 11.9-12.2 11.7-12.0 11.6-11.9 |
12.4
12.3 12.1 12.0 11.9 11.7 |
16.2-18.1
15.2-17.1 14.4-16.2 13.7-15.4 13.1-14.7 12.6-14.0 |
17.0
16.0 15.1 14.3 13.7 13.1 |
15.7-17.3
14.9-16.5 14.2-15.8 13.5-15.1 13.0-14.4 12.5-13.9 |
16.4
15.6 14.8 14.1 13.5 13.0 |
16.8-19.3
15.6-18.0 14.6-16.8 13.8-15.8 13.2-15.0 12.7-14.3 |
17.8
16.6 15.5 14.6 13.9 13.2 |
11.7-12.0
11.6-11.9 11.5-11.7 11.4-11.6 11.3-11.5 11.3-11.5 |
11.8
11.7 11.6 11.5 11.4 11.4 |
| 2 x 4 furring with R13 batt & ½ in. (13 mm) gypsum board on furring | 85
95 105 115 125 135 |
13.2-13.5
13.1-13.4 12.9-13.2 12.8-13.1 12.7-13.0 12.5-12.9 |
13.3
13.2 13.0 12.9 12.8 12.7 |
17.1-19.0
16.1-18.0 15.3-17.1 14.6-16.3 14.0-15.6 13.5-15.0 |
17.9
16.9 16.0 15.2 14.6 14.1 |
16.7-18.3
15.8-17.5 15.1-16.7 14.5-16.0 13.9-15.4 13.5-14.8 |
17.4
16.5 15.7 15.1 14.5 14.0 |
17.7-20.2
16.6-18.9 15.6-17.8 14.8-16.8 14.1-15.9 13.6-15.2 |
18.8
17.5 16.4 15.5 14.8 14.2 |
12.7-12.9
12.5-12.8 12.4-12.7 12.3-12.6 12.3-12.5 12.2-12.4 |
12.8
12.6 12.5 12.4 12.3 12.3 |
b Values apply when all masonry cores are filled completely. Grout density is 140 pcf (2243 kg/m3). Lightweight grouts, which will provide higher R-values, are also available in some areas.
c Installed over wood furring. Includes ½ in. (13 mm) gypsum board and nonreflective air space.
d Installed over wood furring, Includes ½ in. (13 mm) gypsum board and reflective air space.
| Table 4 - R-Values for 10 in. (254 mm) Concrete Masonry Walls, hr.ft2.oF/Btua |
| Cores filled withb: |
| Construction | Density of concrete, | Cores
empty |
Loose-fill insulation Perlite Vermiculite |
Polyurethane
foamed insulation |
Solid grouted |
| pcf | range | mid | range | mid | range | mid | range | mid | range | mid | |
| Exposed block,
both sides |
85
95 105 115 125 135 |
2.5-2.9
2.4-2.7 2.2-2.5 2.1-2.4 1.9-2.3 1.8-2.1 |
2.7
2.5 2.3 2.2 2.1 2.0 |
7.5-9.9
6.3-8.7 5.2-7.5 4.4-6.5 3.7-5.6 3.1-4.9 |
8.5
7.2 6.1 5.2 4.4 3.7 |
7.0-9.1
6.0-8.0 5.0-7.0 4.2-6.2 3.6-5.4 3.0-4.7 |
7.9
6.8 5.8 5.0 4.3 3.6 |
8.2-11.3
6.7-9.7 5.5-8.2 4.6-7.0 3.8-6.0 3.2-5.1 |
9.5
7.9 6.6 5.5 4.6 3.9 |
2.1-2.4
1.9-2.2 1.8-2.1 1.7-2.0 1.6-1.9 1.5-1.8 |
2.2
2.0 1.9 1.8 1.7 1.6 |
| ½ in. (13 mm) gypsum board on furring | 85
95 105 115 125 135 |
3.9-4.3
3.8-4.1 3.6-3.9 3.5-3.8 3.3-3.7 3.2-3.5 |
4.1
3.9 3.7 3.6 3.5 3.4 |
8.9-11.3
7.7-10.1 6.6-8.9 5.8-7.9 5.1-7.0 4.5-6.3 |
9.9
8.6 7.5 6.6 5.8 5.1 |
8.4-10.5
7.4-9.4 6.4-8.4 5.6-7.6 5.0-6.8 4.4-6.1 |
9.3
8.2 7.2 6.4 5.7 5.0 |
9.6-12.7
8.1-11.1 6.9-9.6 6.0-8.4 5.2-7.4 4.6-6.5 |
10.9
9.3 8.0 6.9 6.0 5.3 |
3.5-3.8
3.3-3.6 3.2-3.5 3.1-3.4 3.0-3.3 2.9-3.2 |
3.6
3.4 3.3 3.2 3.1 3.0 |
| 1 in. (25 mm) expanded polystyrenec | 85
95 105 115 125 135 |
7.9-8.3
7.8-8.1 7.6-7.9 7.5-7.8 7.3-7.7 7.2-7.5 |
8.1
7.9 7.7 7.6 7.5 7.4 |
8.9-11.3
7.7-10.1 6.6-8.9 5.8-7.9 5.1-7.0 4.5-6.3 |
13.9
12.6 11.5 10.6 9.8 9.1 |
12.4-14.5
11.4-13.4 10.4-12.4 9.6-11.6 9.0-10.8 8.4-10.1 |
13.3
12.2 11.2 10.4 9.7 9.0 |
13.6-16.7
12.1-15.1 10.9-13.6 10.0-12.4 9.2-11.4 8.6-10.5 |
14.9
13.3 12.0 10.9 10.0 9.3 |
7.5-7.8
7.3-7.6 7.2-7.5 7.1-7.4 7.0-7.3 6.9-7.2 |
7.6
7.4 7.3 7.2 7.1 7.0 |
| 1 in. (25 mm) extruded polystyrenec | 85
95 105 115 125 135 |
8.9-9.3
8.8-9.1 8.6-8.9 8.5-8.8 8.3-8.7 8.2-8.5 |
9.1
8.9 8.7 8.6 8.5 8.4 |
12.9-15.3
11.7-14.1 10.6-12.9 9.8-11.9 9.1-11.0 8.5-10.3 |
14.9
13.6 12.5 11.6 10.8 10.1 |
13.4-15.5
12.4-14.4 11.4-13.4 10.6-12.6 10.0-11.8 9.4-11.1 |
14.3
13.2 12.2 11.4 10.7 10.0 |
14.6-17.7
13.1-16.1 11.9-14.6 11.0-13.4 10.2-12.4 9.6-11.5 |
15.9
14.3 13.0 11.9 11.0 10.3 |
8.5-8.8
8.3-8.6 8.2-8.5 8.1-8.4 8.0-8.3 7.9-8.2 |
8.6
8.4 8.3 8.2 8.1 8.0 |
| 1 in. (25 mm) polyiso-cyanurated | 85
95 105 115 125 135 |
12.4-12.7
12.2-12.6 12.1-12.4 11.9-12.3 11.8-12.1 11.7-12.0 |
12.5
12.4 12.2 12.1 11.9 11.8 |
13.9-16.3
12.7-15.1 11.6-13.9 10.8-12.9 10.1-12.0 9.5-11.3 |
18.4
17.1 16.0 15.1 14.3 13.6 |
16.9-18.9
15.8-17.9 14.9-16.9 14.1-16.0 13.5-15.2 12.9-14.6 |
17.8
16.7 15.7 14.9 14.1 13.5 |
18.0-21.1
16.6-19.5 15.4-18.1 14.4-16.9 13.7-15.9 13.0-14.9 |
19.3
17.8 16.5 15.4 14.5 13.7 |
11.9-12.2
11.8-12.1 11.7-11.9 11.6-11.8 11.5-11.7 11.4-11.6 |
12.1
11.9 11.8 11.7 11.6 11.5 |
| 2 x 4 furring with R13 batt & ½ in. (13 mm) gypsum board on furring | 85
95 105 115 125 135 |
13.3-13.7
13.2-13.5 13.0-13.3 12.9-13.2 12.7-13.1 12.6-12.9 |
13.5
13.3 13.1 13.0 12.9 12.8 |
17.4-19.8
16.1-18.5 15.1-17.4 14.3-16.4 13.5-15.5 13.0-14.7 |
19.3
18.0 16.9 16.0 15.2 14.5 |
17.8-19.9
16.8-18.8 15.8-17.8 15.0-17.0 14.4-16.2 13.8-15.5 |
18.7
17.6 16.6 15.8 15.1 14.4 |
19.0-22.1
17.5-20.5 16.3-19.0 15.4-17.8 14.6-16.8 14.0-15.9 |
20.3
18.7 17.4 16.3 15.4 14.7 |
12.9-13.2
12.7-13.0 12.6-12.9 12.5-12.8 12.4-12.7 12.3-12.6 |
13.0
12.8 12.7 12.6 12.5 12.4 |
b Values apply when all masonry cores are filled completely. Grout density is 140 pcf (2243 kg/m3). Lightweight grouts, which will provide higher R-values, are also available in some areas.
c Installed over wood furring. Includes ½ in. (13 mm) gypsum board and nonreflective air space.
d Installed over wood furring, Includes ½ in. (13 mm) gypsum board and reflective air space.
| Table 5 - R-Values for 12 in. (305 mm) Concrete Masonry Walls, hr.ft2.oF/Btua |
| Cores filled withb: |
| Construction | Density of concrete, | Cores
empty |
Loose-fill insulation Perlite Vermiculite |
Polyurethane
foamed insulation |
Solid grouted |
| pcf | range | mid | range | mid | range | mid | range | mid | range | mid | |
| Exposed block,
both sides |
85
95 105 115 125 135 |
2.6-3.0
2.4-2.8 2.3-2.6 2.1-2.5 2.0-2.3 1.9-2.2 |
2.8
2.6 2.4 2.3 2.2 2.0 |
9.1-12.1
7.6-10.5 6.3-9.1 5.2-7.9 4.4-6.8 3.6-5.8 |
10.3
8.8 7.4 6.2 5.3 4.4 |
8.5-11.0
7.2-9.7 6.0-8.5 5.1-7.4 4.2-6.5 3.6-5.6 |
9.6
8.2 7.0 6.0 5.1 4.3 |
10.0-13.8
8.2-11.8 6.7-10.0 5.5-8.5 4.5-7.2 3.7-6.1 |
11.5
9.6 8.0 6.6 5.5 4.6 |
2.3-2.6
2.1-2.4 2.0-2.3 1.9-2.2 1.8-2.0 1.7-1.9 |
2.4
2.3 2.1 2.0 1.9 1.8 |
| ½ in. (13 mm) gypsum board on furring | 85
95 105 115 125 135 |
4.0-4.4
3.8-4.2 3.7-4.0 3.5-3.9 3.4-3.7 3.3-3.6 |
4.2
4.0 3.8 3.7 3.6 3.4 |
10.5-13.5
9.0-11.9 7.7-10.5 6.6-9.3 5.8-8.2 5.0-7.2 |
11.7
10.2 8.8 7.6 6.7 5.8 |
9.9-12.4
8.6-11.1 7.4-9.9 6.5-8.8 5.6-7.9 5.0-7.0 |
11.0
9.6 8.4 7.4 6.5 5.7 |
11.4-15.2
9.6-13.2 8.1-11.4 6.9-9.9 5.9-8.6 5.1-7.5 |
12.9
11.0 9.4 8.0 6.9 6.0 |
3.7-4.0
3.5-3.8 3.4-3.7 3.3-3.6 3.2-3.4 3.1-3.3 |
3.8
3.7 3.5 3.4 3.3 3.2 |
| 1 in. (25 mm) expanded polystyrenec | 85
95 105 115 125 135 |
8.0-8.4
7.8-8.2 7.7-8.0 7.5-7.9 7.4-7.7 7.3-7.6 |
8.2
8.0 7.8 7.7 7.6 7.4 |
14.5-17.5
13.0-15.9 11.7-14.5 10.6-13.3 9.8-12.2 9.0-11.2 |
15.7
14.2 12.8 11.6 10.7 9.8 |
13.9-16.4
12.6-15.1 11.4-13.9 10.5-12.8 9.6-11.9 9.0-11.0 |
15.0
13.6 12.4 11.4 10.5 9.7 |
15.4-19.2
13.6-17.2 12.1-15.4 10.9-13.9 9.9-12.6 9.1-11.5 |
16.9
15.0 13.4 12.0 10.9 10.0 |
7.7-8.0
7.5-7.8 7.4-7.7 7.3-7.6 7.2-7.4 7.1-7.3 |
7.8
7.7 7.5 7.4 7.3 7.2 |
| 1 in. (25 mm) extruded polystyrenec | 85
95 105 115 125 135 |
9.0-9.4
8.8-9.2 8.7-9.0 8.5-8.9 8.4-8.7 8.3-8.6 |
9.2
9.0 8.8 8.7 8.6 8.4 |
15.5-18.5
14.0-16.9 12.7-15.5 11.6-14.3 10.8-13.2 10.0-12.2 |
16.7
15.2 13.8 12.6 11.7 10.8 |
14.9-17.4
13.6-16.1 12.4-14.9 11.5-13.8 10.6-12.9 10.0-12.0 |
16.0
14.6 13.4 12.4 11.5 10.7 |
16.4-20.2
14.6-18.2 13.1-16.4 11.9-14.9 10.9-13.6 10.1-12.5 |
17.9
16.0 14.4 13.0 11.9 11.0 |
8.7-9.0
8.5-8.8 8.4-8.7 8.3-8.6 8.2-8.4 8.1-8.4 |
8.8
8.7 8.5 8.4 8.3 8.2 |
| 1 in. (25 mm) polyiso-cyanurated | 85
95 105 115 125 135 |
12.5-12.8
12.3-12.6 12.2-12.5 12.0-12.3 11.9-12.2 11.8-12.1 |
12.6
12.4 12.3 12.1 12.0 11.9 |
19.0-22.0
17.4-20.4 16.2-19.0 15.1-17.7 14.2-16.6 13.5-15.7 |
20.2
18.6 17.3 16.1 15.1 14.3 |
18.4-20.9
17.0-19.6 15.9-18.4 14.9-17.3 14.1-16.3 13.4-15.5 |
19.4
18.1 16.9 15.8 14.9 14.2 |
19.8-23.7
18.0-21.6 16.5-19.9 15.3-18.4 14.4-17.1 13.6-16.0 |
21.4
19.5 17.8 16.5 15.4 14.5 |
12.2-12.5
12.0-12.3 11.9-12.2 11.8-12.0 11.7-11.9 11.6-11.8 |
12.3
12.1 12.0 11.9 11.8 11.7 |
| 2 x 4 furring with R13 batt & ½ in. (13 mm) gypsum board on furring | 85
95 105 115 125 135 |
13.4-13.8
13.2-13.6 13.1-13.4 12.9-13.3 12.8-13.1 12.7-13.0 |
13.6
13.4 13.2 13.1 13.0 12.8 |
19.9-22.9
18.4-21.3 17.1-19.9 16.0-18.7 15.2-17.6 14.4-16.6 |
21.1
19.6 18.2 17.0 16.1 15.2 |
19.3-21.8
18.0-20.5 16.8-19.3 15.9-18.2 15.0-17.3 14.4-16.4 |
20.4
19.0 17.8 16.8 15.9 15.1 |
20.8-24.6
19.0-22.6 17.5-20.8 16.3-19.3 15.3-18.0 14.5-16.9 |
22.3
20.4 18.8 17.4 16.3 15.4 |
13.1-13.4
12.9-13.2 12.8-13.1 12.7-13.0 12.6-12.8 12.5-12.7 |
13.2
13.1 12.9 12.8 12.7 12.6 |
a Notes: (hr.ft2.oF/Btu) (0.176) = m2.K/W. Mortar joints are in. (10 mm) thick, with face shell mortar bedding assumed. Unit dimensions based on Standard Specification for Loadbearing Concrete Masonry Units, ASTM C 90 (ref. 2). Surface air films are included.
b Values apply when all masonry cores are filled completely. Grout density is 140 pcf (2243 kg/m3). Lightweight grouts, which will provide higher R-values, are also available in some areas.
c Installed over wood furring. Includes ½ in. (13 mm) gypsum board and nonreflective air space.
d Installed over wood furring, Includes ½ in. (13 mm) gypsum board and reflective air space.
R-VALUES FOR PARTIALLY GROUTED MASONRY
For partially grouted walls, the values in Tables 2 through 5 must be modified. The first step is to determine how much of the wall area is grouted, from Table 1. The U-factor of the wall is calculated from the area-weighted average of the U-factor of the grouted area and the U-factor of the ungrouted area as follows:
U = (agr x Ugr ) + (aungr x Uungr ) and R = 1/U
where:
agr = fractional grouted area of wall
aungr = fractional ungrouted area of wall
R = total thermal resistance of wall, hrft2.oF/Btu (m2.K/W)
U = total thermal conductance of wall, Btu/hr.ft2.oF (W/m2.K)
Ugr = conductance of fully grouted wall, Btu/hr.ft2.oF (W/m2.K)
Uungr = conductance of ungrouted wall, Btu/hr.ft2.oF (W/m2.K)
For example, consider an 8 in. (203mm) wall composed of hollow 105 lb/ft3 (1682kg/m3) concrete masonry, and grouted at 48 in. (1219 mm) o.c. both vertically and horizontally. The ungrouted cores contain perlite loose fill insulation.
From Table 1, 31% of the wall is grouted and 69% contains insulation. From Table 3, the R-value for a solidly grouted concrete masonry wall is 1.7 hr.ft2.oF/Btu (0.30 m2.K/W). The corresponding U-factor is 1/1.7 or 0.588 Btu/hr.ft2.oF (3.3 W/m2.K). Again from Table 3, a wall containing perlite loose fill insulation has an R-value of 5.2, with a corresponding U-factor of 0.192. The U-factor and R-value of the wall are calculated as follows:
U = agr x Ugr + aungr x Uungr
= (0.31 x 0.588) + (0.69 x 0.192)
= 0.315 Btu/hr.ft2.oF (1.79 W/ m2.K)
R = 1/U = 1/0.315 = 3.2 hr.ft2.oF/Btu (0.56 m2.K/W)
| Table 6 - Thermal Data Used
To Develop Tables |
| Material | Thermal resistivity (R-value per inch), hr.ft2.0F/Btu. in (m.K/W) |
| Vermiculite
Perlite Expanded polystyrene Extruded polystyrene Cellular polyisocyanurate, gas- impermeable facer Polyurethane foamed-in-place insulation Wood Concrete: 85 pcf 95 pcf 105 pcf 115 pcf 125 pcf 135 pcf 140 pcf Mortar Material |
2.27 (15.7)
3.13 (21.7) 4.00 (27.7) 5.00 (34.7) 7.04 (48.8) 5.91 (41.0) 1.00 (6.9) 0.23 - 0.34 (1.6 - 2.4) 0.18 - 0.28 (1.2 - 1.9) 0.14 - 0.23 (0.97 - 1.6) 0.11 - 0.19 (0.76 - 1.3) 0.08 - 0.15 (0.55 - 1.0) 0.07 - 0.12 (0.49 - 0.83) 0.06 - 0.11 (0.40 - 0.78) 0.20 (1.4) R-value, hr.ft2.0F/Btu. (m.K/W) |
| ½ in. (13 mm) gypsum
wallboard
Inside surface air film Outside surface air film Nonreflective air space Reflective air space |
0.45 (0.08)
0.68 (0.12) 0.17 (0.03) 0.97 (0.17) 2.38(0.42) |
REFERENCES
1. ASHRAE Fundamentals Handbook, Atlanta, GA: American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc., 1993.
National Concrete Masonry Association
2302 Horse Pen Road, Herndon, VA 22071-3499
Reprinted from the TEK Manual for Concrete Masonry
Design and Construction. Copyright NCMA.
For Concrete Masonry Walls
TEK 13-1 (Sound 1998)
Unwanted noise is a major distraction, both in the home as well as the work environment. With each technological advance, more and more different types of noise generating machinery and appliances are finding their way into our everyday lives. This unwanted noise is not only disconcerting, but in many cases may also produce permanent injury to hearing when exposure is for prolonged periods of time, depending upon the intensity of the sound.
Two important elements of sound are frequency and pressure. Frequency is a measure of the number of vibrations or cycles per second (cps). One cycle per second is defined as a hertz (HZ). The measurement of pressure is in decibels (dB). For each 20 decibel increase in sound there is a corresponding tenfold increase in pressure. The human ear has the unique ability to reduce its sensitivity as the pressure increases. Therefore, while a 10 decibel increase in sound results in a threefold increase in pressure, the loudness sensation to the ear is only doubled.
The following provides an indication of the decibel as a measure of sound intensity.
| Decibels | Sound |
| 140
130 120 110 100 90 80 70 60 50 40 30 20 10 3 |
Jet plane takes off
Threshold of discomfort Riveting Thunder - sonic boom Hard rock band Power lawnmower Pneumatic jackhammer Noisy office Average radio Normal conversation Quiet street Quiet conversation Whisper at 4 ft. Normal breathing Threshold of audibility |


All solid materials have a natural frequency of vibrations. If the frequency of a solid is at or near the frequency of the sound which strikes it, the solid will vibrate in sympathy with the sound, and the sound will be re-generated on the opposite side. The is true for all solids, including walls and partitions. The effect is especially noticeable when the wall or partition is light or thin. Conversely, the vibration is effectively stopped if the partition is of heavy, rigid material. Then the natural cycle of vibration will be relatively slow, and only sounds of low frequency will cause sympathetic vibration.
The human ear can perceive sounds as low as 16 cycles per second to as high as 20,000 cycles per second. However, it is most sensitive to sounds between 500 and 5,000 cycles. For human voices speaking in conversational tones, a frequency of approximately 500 cycles per second is assumed.
Because of its mass and rigidity, concrete masonry is especially effective in reducing the transmission of unwanted sound. This is just one of its many attributes which makes it a most desirable building material.
SOUND TRANSMISSION CLASS
Sound transmission class (STC) is a single-figure rating derived in a prescribed manner from sound transmission loss values. The rating provides an estimate of the performance of the partition in certain common sound insulation problems.
The STC of a wall is determined by comparing its transmission loss curve with a set of standard curves, or contours. The standard curve is superimposed over a plot of the sound transmission loss curve (Figure 1) and shifted upward or downward relative to the test curve until some of the measured TL values of the test specimen fall below those of the STC contour and the following conditions are fulfilled:
1. The sum of the deficiencies (deviations below the contour) shall not be greater than 32 dB, and
2. The maximum deficiency at a single test point shall not exceed 8 dB.
When the contour is adjusted to the highest value that meets the above criteria, the sound transmission class is taken to be the transmission loss value, measured in decibels (dB), corresponding to the intersection of the standard contour and the 500 cycle per second (cps) frequency line.
DESIGN AND CONSTRUCTION
In addition to STC values for walls, there are other factors that have an effect on the acoustical environment of a building. Outside noise levels need to be considered. Low background noise levels, such as exist in rural areas, may indicate the need for partition walls to have a higher STC requirement. Another item that is important to noise insulation is wall layout. In apartment construction, an in-line arrangement, where each apartment will have only one common wall, is preferred. "Mirror-plan" arrangement will generally result in quieter areas, such as bedrooms being located adjacent to each other, and noisy areas, such as kitchens abutting each other. Door and window arrangement may also have an effect on the acoustical environment. Locating apartment doors so that they are not directly opposite each other will diffuse a portion of noise that would otherwise be able to transmit directly across a hall. Windows in exterior walls should be located as far away from common walls as possible in order to
help diffuse noise that may travel from one window to another.
Openings placed in common walls, such as electrical fixtures, plumbing pipes, ducts, and medicine cabinets, are a potential source for noise leaks. Figures 3 and 4 of the TEK illustrate possible methods to control noise penetration through proper detailing and construction.
BUILDING CODE REQUIREMENTS
The model building codes all have similar requirements regulating sound transmission control for partitions that separate adjacent units in multi-family dwellings and similar partitions that separate adjacent units in multi-family dwellings and similar partitions that separate dwelling units from public areas, service areas, or commercial facilities. In the BOCA Code, and the appendix of the Standard Building Code, the requirement is that all partitions serving the above purpose shall have a sound transmission class of not less than 45 Db for air-borne noise when tested in accordance with ASTM E90. The Appendix of the Uniform Building Code establishes a lower limit of 50dB for the same applications.
SOUND TRANSMISSION CLASS OF CONCRETE MASONRY
Kodaras Acoustical Laboratories (KAL) was commissioned to conduct sound transmission loss tests on walls ranging in weight from 22 pounds per square foot to 79 pounds per square foot. Surfaces of the walls were sealed on one or both sides with paint, while others were plastered. The STC values of these walls were then determined in accordance with ASTM E413, Standard Classification of Sound Transmission Class.
| Table 1 - Summary Of STC Data Of Concrete Masonry Walls |
| No. | Test Designation | Wall
Weight
lbs./sq. ft. |
STC
dB |
| 1
2 3 4 5 6 7 8 9 10 11 12 |
KAL
KAL KAL KAL KAL KAL KAL KAL KAL KAL KAL KAL |
1379-5-72
1709-74 933-2-70 1379-3-72 369-5-66 359-7-66 365-3-66 1379-1-72 1144-2-71 1144-3-71 1023-2-71 1023-9-71 |
22
28 28 29 30 30 32 39 43 53 73 79 |
43
43 46 44 46 48 43 48 49 52 55 56 |
Further tests on companion walls have indicated the effect of adding gypsum board to the surface of the walls. The results of these tests indicated an increase of approximately 2 points to the STC value of the walls. An additional increase may be obtained if the gypsum board is mounted on resilient channels.
For Concrete Masonry Walls
1.0 - SCOPE
These provisions cover requirements for sound transmission class (STC) rated concrete masonry walls and supplement the concrete masonry requirements of the general building code.
FSTC = Field Sound Transmission Class
STC = Sound transmission class
w = Wall weight, psf
wreq = Required wall weight, psf
decibel, dB - the term used to identify ten times the common logarithm of the ratio of two like quantities proportional to power or energy.
field sound transmission class, FSTC - sound transmission class calculated using values of field transmission loss.
sound transmission class, STC - a single-number rating using values of sound transmission loss. It provides an estimate of the performance of a partition in certain common sound insulation problems.
sound transmission loss, TL - a partition, in a specified frequency band, the decibel difference between the airborne sound power incident on the partition and radiated on the other side.
wall weight - the weight of the masonry partition including any core fill, surface coatings, or coverings. The weight of cavity walls shall be calculated as the sum of the weights of the wythes.
Materials used in the construction shall conform to the following ASTM specifications.
Masonry Units:
ASTM C 55, Standard Specification for Concrete Building Brick; ASTM C 73, Standard Specification for Calcium Silicate Face Brick (Sand-Lime Brick); ASTM C 90 Standard Specification for Load-Bearing Concrete Masonry Units; ASTM C 129, Standard Specification for Non-Loadbearing Concrete Masonry Units, ASTM C 744, Standard Specification for Prefaced Concrete and Calcium Silicate Masonry Units
Mortar:
ASTM C 270, Standard Specification for Mortar for Unit Masonry
Grout:
ASTM C 476, Standard Specification for Grout Reinforced and Nonreinforced Masonry
Joint Sealants:
ASTM C 920, Standard Specification for Elastomeric Joint Sealants
5.0 - CONSTRUCTION
Construction shall be in accordance with the requirements of the general building code and this section.
5.1 Placing Mortar and Units:
5.1.1 Hollow units shall be placed so that the face shells of bed joints are fully
mortared and head joints are mortared a minimum distance from each face equal to the face shell thickness of the unit.5.1.2 Solid units shall be placed with full bed and head joints such that mortar fills the joints from one face of the unit to the opposite face.
5.1.3 Holes, cracks, and voids in the masonry shall be filled.
5.2 Sealing Openings and Joints
5.2.1 Through penetration openings to accommodate pipes, air ducts, electrical outlets, etc., shall be completely sealed. Prior to sealing around openings, gaps shall be filled with foam, cellulose fiber, glass fiber, or mineral wool in accordance with Figure 3.
5.2.2 Electrical outlets and other fixtures installed in masonry walls shall be sealed to prevent airborne sound from entering the wall in accordance with Figure 3.
5.2.3 Control joints and joints between intersecting walls shall be sealed in accordance with one of the methods illustrated in Figure 4.
5.2.4 Joints between the top of walls and roof or floor assemblies shall be sealed. The joint space behind the sealant shall be filled with mortar, grout, foam, cellulose fiber, glass fiber, or mineral wool.
5.3 Surface Sealants:
5.3.1 All walls shall be sealed with acrylic, oil, or cement based paints or plaster; or other suitable sealants.
6.0 - QUALITY ASSURANCE
The work shall be inspected for compliance with these requirements.
6.1 Acceptance - walls complying with these requirements shall be accepted. Walls which fail to meet one or more of these requirements shall be brought into compliance or may be accepted provided the FSTC rating determined in accordance with ASTM E 413 equals or exceeds the required field STC rating.
7.0 - MINIMUM WALL THICKNESS
The minimum nominal thickness of walls shall be 4 inches.
8.0 - CALCULATED STC RATINGS
8.1 The calculated sound transmission class rating of a concrete masonry wall system shall be determined in accordance with Equation 1.
STC = 23(w)0.2 Eqn. 1
8.2 For a given STC, the required weight of the wall system shall be determined in accordance with equation 2.
Wreq = (STC/23)5 Eqn. 2
REFERENCES
(1) ASTM E 90 Laboratory Measurement of Airborne-Sound Transmission Loss of Building Partitions
(2) ASTM E 413 Standard Classification of Sound Transmission Class
(3) Noise Control in Buildings, National Research Council of Canada, 1987
(4) Kodaras Acoustical Laboratories
2302 Horse Pen Road, Herndon, VA 22071-3499
Reprinted from the TEK Manual for Concrete Masonry
Design and Construction. Copyright NCMA.